Parameters supported – Rockwell Automation 825-MDN Smart Motor Manager DeviceNet Communication Card User Manual User Manual

Page 37

Advertising
background image

Publication 825-UM002A-EN-P - December 2000

A-15

Parameters Supported

➊ Values 254 and 255 indicate an error (PT100 short circuit or open circuit).

❷ Available with SMM version 3.11 (or higher) / 825-MDN version 6.001 (or higher) product combination only.

➌ Available with SMM version 2.xx (and lower).

Parameter No.

®=read-only

Parameter

Name

Object

Mapping

Description

Data
Type

Units

Min/Max

Default

1 ®

I Motor

0x2C-1-5

AvgPhaseCurrent in % of FLC - Average
of 3 Currents

INT

% FLC

0…1200

0

2 ® Th

Utilize

0x2C-1-7

%

Thermal

Capacity

Utilization

USINT

%

0…100

0

3 ®

I Motor L1

0x2C-1-8

PhaseCurrentL1 in % of FLC - Actual
motor phase current L1

INT

% FLC

0…1200

0

4 ®

I Motor L2

0x2C-1-9

PhaseCurrentL2 in % of FLC - Actual
motor phase current L2

INT

% FLC

0…1200

0

5 ®

I Motor L3

0x2C-1-10

PhaseCurrentL3 in % of FLC - Actual
motor phase current L3

INT

% FLC

0…1200

0

6 ®

Time to Trip

0x2C-1-102

Time to trip

UINT

seconds

0…9999

9999

7 ®

Asymmetry

0x2C-1-6

% Phase Imbalance

USINT

%

0…100

0

8 ®

I Earth-H

0x2C-1-103

Ground fault current via Holmgreen
Method in % of actual motor current

USINT

%

0…100

0

9 ®

I Earth-C

0x2C-1-11

Ground fault current via core balance
transformer

UINT

mA

0…500

0

10 ®

T Ambient

0x0F-10-1

Platinum RTD Ambient Temp. Sensor

USINT

°

C 0…255

0

11 ®

PT100 #1

0x0F-11-1

Platinum RTD Temp Sensor #1

USINT

°

C 0…255

0

12 ®

PT100 #2

0x0F-12-1

Platinum RTD Temp Sensor #2

USINT

°

C 0…255

0

13 ®

PT100 #3

0x0F-13-1

Platinum RTD Temp Sensor #3

USINT

°

C 0…255

0

14 ®

PT100 #4

0x0F-14-1

Platinum RTD Temp Sensor #4

USINT

°

C 0…255

0

15 ®

PT100 #5

0x0F-15-1

Platinum RTD Temp Sensor #5

USINT

°

C 0…255

0

16 ®

PT100 #6

0x0F-16-1

Platinum RTD Temp Sensor #6

USINT

°

C 0…255

0

17 ®

PT100 max

0x0F-17-1

Platinum RTD Max Temp of all Sensors

USINT

°

C 0…255

0

18 ®

Actual Trip

0x2C-1-104

Actual Trip Cause - Bit-string

UINT

0…0xFFFF

0

19 ®

Actual Warning

0x2C-1-105

Actual Warning Cause - Bit-string

UINT

0…0xFFFF 0

20 ®

Control Inputs

0x29-1-137

State of Control Inputs #1, #2

UINT

0…0x101

0

21

Full Load Curr

0x2C-1-3

TripFLCSet - Overload FLC

UDINT

0.01 A

50…200,000

2000

21

Full Load Curr

0x2C-1-3

TripFLCSet - Overload FLC

UINT

0.01 A

50…63,000

2000

22

Locked Rot Curr

0x2C-1-106

Locked Rotor to FLC Current Ratio
(2.5…12.0 times FLC)

USINT

times 0.1FLC 25…120

60

23

Locked Rot Time

0x2C-1-165

Maximum Locked Rotor Time

UINT

seconds

1…600

10

24

Thermal Trip Rel

0x29-1-100

Thermal Trip Relay Assignment, 0=main
7=None

USINT

0, 7

0

25

Thermal Warning

0x2C-1-107

Thermal Warning, 0=OFF 1=ON

BOOL

0…1

0

26

Th Warning Level

0x2C-1-108

Thermal Warning Level

USINT

%

50…99

75