Instance attributes, continued, Fault/trip cause word bitstring, Warning cause word bitstring – Rockwell Automation 825-MDN Smart Motor Manager DeviceNet Communication Card User Manual User Manual

Page 62

Advertising
background image

Publication 825-UM002A-EN-P - December 2000

A-40

Instance Attributes, Continued

➊ Available with SMM version 3.11 (or higher) / 825-MDN version 6.001 (or higher) product combination only.

Fault/Trip Cause Word Bitstring

Warning Cause Word Bitstring

Attribute

ID

Access

Rule

Name (param. #)

Data
Type

Min/Max

Units

Default

Description

160

Get/Set

drs_prot (#116)

BOOL

0…1

0=OFF

0

Phase reversal trip, on/off

161

Get/Set

pas_prot (#118)

BOOL

0…1

0=OFF

0

Phase loss trip, on/off

162

Get/Set

prim_ct_ (#206)

BOOL

0…1

0=NO

0

Primary current transformer used, no/yes

163

Get/Set

ct_ratio (#207)

UINT

1…2000

1

Current ratio of primary current
transformer

164

Get/Set

isol_cl_ (#208)

USINT

0…2

0

Motor insulation class 0=B, 1=E, 2=F

168

Get/Set

prim2_CT (#227)

BOOL

0…1

0=NO

0

Second primary CT enable

169

Get/Set

CT2_ratio (#228)

UINT

1…2000

1

Second primary-to-secondary CT ratio

170

Get/Set

corCTrat (#229)

UINT

1…2000

1

Core balance CT primary-to-secondary
ratio

171

Get

sp_sw_ti (#232)

USINT

1…50

0.1 sec.

5

Speed switch trip delay

Bit15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

wrong
setting

0

short
circuit
trip

current
transformer

phase
loss

locked
rotor

Asym-
metry

phase
reverse

thermal earth

fault

under-
load

thermistor PT100 start

inhibit

over
starting
time

fault
in
actual
values

Bit15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

wrong
setting

0

0

0

0

overcurrent asymmetry

0

thermal earth fault underload 0

PT100

0

0

0