Parameters Supported, Continued

➊ Available with SMM version 3.11 (or higher) / 825-MDN version 6.001 (or higher) product combination.

❷ Available with SMM version 2.xx (and lower).

Parameter

No.

®=read-only

Parameter Name

Object

Mapping

Description

Data
Type

Units

Min/Max

Default

100

PT100 Prot #1

0x0F-100-1

PT100 Protection, 0=Not Disable
1=Disable

BOOL

0…1

0

101

Control Input #2

0x29-1-128

Control Input #2, 0=OFF 1=ON

BOOL

0…1

0

102

Delay Aux Rel #3

0x29-1-129

Time Delay of Auxiliary Relay #3, 0=OFF

1=ON

BOOL

0…1

0

103

On Delay Aux #3

0x29-1-130

ON Delay of Auxiliary Relay #3

USINT

seconds

0…240

1

104

Off Delay Aux #3

0x29-1-131

OFF Delay of Auxiliary Relay #3

USINT

seconds

0…240

2

105

2nd FLC Enable

0x2C-1-152

2nd Rated Motor Current, 0=OFF 1=ON BOOL

0…1

0

106

2nd FLC

0x2C-1-153

2nd Rated Motor Current, Value

(0.50…2000.00 A)

UDINT

0.01 A

50…200,000 2000

106

2nd FLC

0x2C-1-153

2nd Rated Motor Current, Value
(0.50…630.00 A)

UINT

0.01 A

50…63,000

2000

107

Disable Prot #2

0x29-1-132

Disable Protective Functions, 0=OFF
1=ON

BOOL

0…1

0

108

As Prot #2

0x2C-1-154

Asymmetry Protection, 0=Not Disable

1=Disable

BOOL

0…1

0

109

OC Prot #2

0x2C-1-155

Overcurrent / Locked-Rotor Protection,
0=Not Disable 1=Disable

BOOL

0…1

0

110

EF Prot #2

0x2C-1-156

Earth Fault Protection, 0=Not Disable

1=Disable

BOOL

0…1

0

111

SC Prot #2

0x2C-1-157

Short Circuit Protection, 0=Not Disable
1=Disable

BOOL

0…1

0

112

UL Prot #2

0x2C-1-158

Underload Protection, 0=Not Disable
1=Disable

BOOL

0…1

0

113

St Inhib Prot #2

0x2C-1-159

Limiting the Starts Per Hour, 0=Not

Disable 1=Disable

BOOL

0…1

0

114

PTC Prot #2

0x0F-114-1

PTC Protection, 0=Not Disable
1=Disable

BOOL

0…1

0

115

PT100 Prot #2

0x0F-115-1

PT100 Protection, 0=Not Disable

1=Disable

BOOL

0…1

0

116

Phase-Rever Trip

0x2C-1-160

Phase Reversal Trip, 0=OFF 1=ON

BOOL

0…1

0

117

Phase-Rever Rel

0x29-1-133

Phase Reversal Trip Relay Assignment

USINT

0…7

0

118

Phase Loss Trip

0x2C-1-161

Phase Loss Trip, 0=OFF 1=ON

BOOL

0…1

0

119

Phase Loss Rel

0x29-1-134

Phase Loss Trip, Relay Assignment

USINT

0…7

0

120

PT100 Prot

0x0F-120-1

PTC Protection, 0=OFF 1=ON

BOOL

0…1

0

121

PT100 #1 Trip

0x0F-121-1

PT100 #1 Trip, 0=OFF 1=ON

BOOL

0…1

0

122

#1 Trip Temp

0x0F-122-1

PT100 #1 Trip, Temperature

USINT

°

C 50…200

50