Using the devicenet status display – Rockwell Automation 825-MDN Smart Motor Manager DeviceNet Communication Card User Manual User Manual

Page 20

Advertising
background image

Publication 825-UM002A-EN-P - December 2000

4-2 Troubleshooting

Using the DeviceNet Status
Display

7KH 'HYLFH1HW 6WDWXV 'LVSOD\ SURYLGHV VWDWXV LQIRUPDWLRQ RQ &RPPXQLFDWLRQ

&DUG RSHUDWLRQV 7KH WURXEOHVKRRWLQJ FKDUW EHORZ VKRZV KRZ WR XVH WKH

'HYLFH1HW 6WDWXV 'LVSOD\ WR GHWHFW DQG FRUUHFW FRPPRQ RSHUDWLRQ SUREOHPV

Status
Code

What it Means:

What to do:

00

The Communication card is not
receiving power from the
network.

Check DeviceNet power and
cable connections and the
power connection on the
DeviceNet terminal block.

01

Device is on-line but not
allocated to a master.

Check DeviceNet master for
correct Communication Card
configuration information (node
address, input bytes, output
bytes).

02

Normal operating state and
device is allocated to a master.

No action required.

03

I/O connection timed out.

Reset device and/or DeviceNet
master device.

04

Diagnostics failed on powerup/
reset.

Internal fault. Cycle power to the
drive and network. If the fault
still exists, return the
Communication Card for repair.

Duplicate DeviceNet node
address (Two nodes cannot
have the same address).

Use the SET VALUES menu to
locate the STATION NUMBER
and change to a valid unused
address and reset by cycling
device power.

Invalid data rate.

Use the SET VALUES menu to
locate the BAUD RATE to the
network data rate and reset by
cycling device power.

IMPORTANT

,I WKH 'HYLFH1HW 6WDWXV 'LVSOD\ GRHV QRW DSSHDU RQ WKH

/&' FKHFN IRU SURSHU LQVWDOODWLRQ RI WKH &RPPXQLFDWLRQ

&DUG LQ WKH 600 DIWHU UHPRYLQJ SRZHU

IMPORTANT

&RQWDFW WKH QHDUHVW $OOHQ%UDGOH\ VDOHV RIILFH LI D VWDWXV

FRGH RWKHU WKDQ WKRVH OLVWHG LV UHWXUQHG