Parameters supported, continued – Rockwell Automation 825-MDN Smart Motor Manager DeviceNet Communication Card User Manual User Manual

Page 46

Advertising
background image

Publication 825-UM002A-EN-P - December 2000

A-24

Parameters Supported, Continued

Parameter

No.

®=read-only

Parameter Name

Object

Mapping

Description

Data
Type

Units

Min/
Max

Default

232

®

Sp Sw Trip Delay

0x2C-1-171

Speed Switch Trip Delay

USINT

0.1 s

1…50

5

233

®

SMM Revision

0xB4-1-12

SMM/CET4 firmware revision

UINT

234

Aux2 Pr FltState

0x29-1-142

Aux relay #2 behavior on a trip condition.
0 = “Go to Value”, 1= “Hold Last State”

BOOL

0…1

0

235

Aux2 Pr FltValue

0x29-1-143

Go To Value setting for parameter #234.
0 = OFF, 1= On

BOOL

0…1

0

236

Aux2 Dn FltState

0x29-1-144

Aux relay #2 behavior on a comm. fault
condition. 0 = “Go to Value”, 1= “Hold Last
State”

BOOL

0…1

0

237

Aux2 Dn FltValue

0x29-1-145

Go To Value setting for parameter #236.
0 = OFF, 1= On

BOOL

0…1

0

238

Aux2 Dn IdlState

0x29-1-146

Aux relay #2 behavior on a comm. idle
condition. 0 = “Go to Value”, 1= “Hold Last
State”

BOOL

0…1

0

239

Aux2 Dn IdlValue

0x29-1-147

Go To Value setting for parameter #238.
0 = OFF, 1= On

BOOL

0…1

0

240

Aux3 Pr FltState

0x29-1-148

Aux relay #3 behavior on a trip condition.
0 = “Go to Value”, 1= “Hold Last State”

BOOL

0…1

0

241

Aux3 Pr FltValue

0x29-1-149

Go To Value setting for parameter #240.
0 = OFF, 1= On

BOOL

0…1

0

242

Aux3 Dn FltState

0x29-1-150

Aux relay #3 behavior on a comm. fault
condition. 0 = “Go to Value”, 1= “Hold Last
State”

BOOL

0…1

0

243

Aux3 Dn FltValue

0x29-1-151

Go To Value setting for parameter #242.
0 = OFF, 1= On

BOOL

0…1

0

244

Aux3 Dn IdlState

0x29-1-146

Aux relay #3 behavior on a comm. idle
condition. 0 = “Go to Value”, 1= “Hold Last
State”

BOOL

0…1

0

245

Aux3 Dn IdlValue

0x29-1-153

Go To Value setting for parameter #244.
0 = OFF, 1= On

BOOL

0…1

0