AC Input Drive Installation Kits

The following kits are available to assist you with installation of drive
components in your enclosure. Note that certain kits are required for proper
installation and for UL certification.

No. Kit

Frame 8 Equivalent

Frame 9 Equivalent

Frame 10 Equivalent

Description

Notes

Catalog Number

Qty. Catalog Number

Qty. Catalog Number

Qty.

Converter (AC Input) Field
Termination

20-750-BUS2-F8

1

20-750-BUS2-F9

1

20-750-BUS2-F10

1

Provides power wiring connection.

(4)

(5)

Inverter (AC Output) Field
Termination

20-750-BUS3-F8

1

20-750-BUS3-F9

1

20-750-BUS3-F10

1

Inverter (DC Bus) Field
Termination - 400/480V

20-750-BUS4-F8

(1)

1

20-750-BUS4-F9

(3)

1

20-750-BUS4-F10

(3)

1

Inverter (DC Bus) Field
Termination - 600/690V

1

20-750-BUS6-F9

(3)

1

20-750-BUS6-F10

(3)

1

Mounting, Back Panel

20-750-MNT2-F8

1

20-750-MNT2-F9

1

20-750-MNT2-F10

1

Drive mounting kit includes four brackets per
drive unit to mount the drive to the back of the
enclosure.

(5)

Mounting, Floor/Rail

20-750-MNT3-F8

1

20-750-MNT3-F9

1

20-750-MNT3-F10

1

Includes bottom rails and hardware to utilize
the roll-out feature of the drive.

(5)

Ducting, Outlet Top

20-750-DUCT2-F8

1

20-750-DUCT2-F8

2

20-750-DUCT2-F8

3

A duct adaptor is provided to direct exhaust air
from the top of the drive. Can be used for
horizontal or vertical installations.

(5)

Ducting, Bottom Inlet

20-750-DUCT4-F8

1

20-750-DUCT4-F8

2

20-750-DUCT4-F8

3

Provides a duct to direct air flow into the
bottom of the cabinet. Requires the Floor/Rail
kit to secure the duct.

Control Pod

20-750-POD1-F8

1

20-750-POD1-F8

1

20-750-POD1-F8

1

Control Pod including Main Control Board and
Fiber Interface Board. Mount in the left most
bay of the drive or remotely (see below).

(4)

(6)

Control Pod Remote Mount

20-750-RPD1-F8

1

20-750-RPD1-F9

1

20-750-RPD1-F10

1

Hardware, fiber-optic, and power supply
cables to remotely mount the control pod up
to 23 m (75 ft) from the drive.

(5)

24V Harness

20-750-PH1-F8

(2)

0

20-750-PH2-F9

1

20-750-PH3-F10

1

For control pod connection in the drive.
Important: Not required if the Remote
Mount kit is ordered.

(7)

Fiber-optic Cable, 0.6 m
(22 in.)

20-750-FCBL1-F8

1

(7)

(8)

Fiber-optic Cable, 2.8 m
(110 in.)

20-750-FCBL1-F10

2

20-750-FCBL1-F10

3

Roll-out Cart

20-750-CART1-F8

1

20-750-CART1-F8

1

20-750-CART1-F8

1

A wheeled roll-out cart that facilitates drive
installation and removal.

(5)

EMC Core

20-750-EMCBUS1-F8

1

20-750-EMCBUS1-F9

1

20-750-EMCBUS1-F10

1

Common mode core kit for converter section
input on AC input drives. To be used with 20-
750-BUS2-F8. EN 61800-3 compliant
installations only.

20-750-EMCCM1-F8

1

20-750-EMCCM1-F8

2

20-750-EMCCM1-F8

3

Common mode core kit for inverter section
output. For AC Input or Common DC Input
drives. EN 61800-3 compliant installations
only.

(1) Optional for Frame 8 equivalent applications; only use if application requires connection to the DC bus (such as a brake or chopper).
(2) Frame 8 equivalent 24V DC harness ships with each drive unit.
(3) Fuses are included.
(4) This kit is required for UL installations.
(5) This is a recommended kit.
(6) This kit is required.
(7) Required when mounting control pod in the drive.
(8) 20-750-PH1-F8 and 20-750-FBCL1-F8 are used for a drive mounted control pod. If the control pod is to be remote mounted up to 23m (75ft), order 20-750-RPD1-F8 kit instead.