PowerFlex 755 IP00, NEMA/UL Open Type Drive

TB1 Terminal Designations

TB2 Terminal Designations (2 Relay Outputs: 2R)

Terminal

Name

Description

Related
Param

(5)

(5) I/O Module parameters will also have a Port designation.

Sh

Shield

Terminating point for wire shields when an
EMC plate or conduit box is not installed.

Sh

Ptc–

Motor PTC (–)

Motor protection device (Positive
Temperature Coefficient).

40
on Port X

Ptc+

Motor PTC (+)

Ao0–

Analog Out 0 (–)

Bipolar, ±10V, 11 bit & sign, 2 k ohm
minimum load.
4-20 mA, 11 bit & sign, 400 ohm maximum
load.

75
on Port X

Ao0+

Analog Out 0 (+)

Ao1–

Analog Out 1 (–)

85
on Port X

Ao1+

Analog Out 1 (+)

–10V

–10 Volt Reference

2k ohm minimum.

10VC

10 Volt Common

For (–) and (+) 10 Volt references.

+10V

+10 Volt Reference

2k ohm minimum.

Ai0–

Analog Input 0 (–)

Isolated

(3)

, bipolar, differential, 11 bit &

sign.
Voltage Mode: ±10V @ 88k ohm input
impedance.
Current Mode: 0-20 mA @ 93 ohm input
impedance.

(3) Differential Isolation - External source must be maintained at less than 160V with respect to PE. Input provides high common mode

immunity.

50, 70
on Port X

Ai0+

Analog Input 0 (+)

Ai1–

Analog Input 1 (–)

60, 70
on Port X

Ai1+

Analog Input 1 (+)

24VC

24 Volt Common

(1)

(1) Not present on 120V versions.

Drive supplied logic input power.
200 mA max. per I/O module
600 mA max per drive

+24V

+24 Volt DC

(1)

Di C

Digital Input Common

Common for Digital Inputs 0…5

Di 0

Digital Input 0

(2)

(2) Digital Inputs are either 24 Volts DC (2262C) or 115 Volts AC (2262D) based on module catalog number. Ensure applied voltage is

correct for I/O module.

24V DC - Opto isolated
Low State: less than 5V DC
High State: greater than 20V DC 11.2 mA DC
115V (132V Max) AC, 50/60 Hz

(4)

- Opto

isolated
Low State: less than 30V AC
High State: greater than 100V AC

(4) For CE compliance use shielded cable. Cable length should not exceed 30 m (98 ft).

1
on Port X

Di 1

Digital Input 1

(2)

Di 2

Digital Input 2

(2)

Di 3

Digital Input 3

(2)

Di 4

Digital Input 4

(2)

Di 5

Digital Input 5

(2)

Relay Out

Terminal

Name

Description

Related
Param

R0NO

Relay 0 N.O.

Relay Normally Open contact output:
240V AC, 24V DC, 2 A max.
General Purpose (Inductive) / Resistive

Relay Normally Closed contact output:
240V AC, 24V DC, 2 A max.
Resistive Only

10, 100,
101, 105,
106
on Port X

R0C

Relay 0 Common

R0NC

Relay 0 N.C.

R1NO

Relay 1 N.O.

20, 110,
111, 115,
116
on Port X

R1C

Relay 1 Common

R1NC

Relay 1 N.C.

Sh
Sh
PTC–
PTC+
Ao0–
Ao0+
Ao1–
Ao1+
–10V
10VC
+10V
Ai0–
Ai0+
Ai1–
Ai1+
24VC
+24V
DiC
Di0
Di1
Di2
Di3
Di4
Di5

R0NO

R0C

R0NC

R1NO

R1C

R1NC