Rockwell Automation Publication 750-IN020C-EN-P - May 2012

PowerFlex 755 IP00, NEMA/UL Open Type Drive

Wire Recommendations

Motor Considerations

Due to the operational characteristics of AC variable frequency drives, motors
with inverter grade insulation systems designed to meet or exceed NEMA MG1
Part 31.40.4.2 standards for resistance to spikes of 1600 volts are recommended.

Guidelines presented in the Wiring and Grounding Guidelines for Pulse Width
Modulated (PWM) AC Drives (publication DRIVES-IN001) must be followed
when using non-inverter grade motors to avoid premature motor failures.

Type

Description

Min. Insulation Rating

Power

(1)(2)

(1) Control and signal wires should be separated from power wires by at least 0.3 meters (1 foot).
(2) The use of shielded wire for AC input power may not be necessary but is always recommended.

Standard

Four tinned copper conductors with XLPE insulation.
Copper braid/aluminum foil combination shield and

tinned copper drain wire.

PVC jacket.

600V,
75 °C (167 °F)