Drive grounding, Ac input common dc input – Rockwell Automation 20G PowerFlex 755 IP00 NEMA/UL Open Drive - Frames 8-10 User Manual

Page 22

Advertising
background image

22

Rockwell Automation Publication 750-IN020C-EN-P - May 2012

PowerFlex 755 IP00, NEMA/UL Open Type Drive

Drive Grounding

A PE termination point is supplied with the Inverter (AC Output) and
Converter (AC Input) termination kits shown on

page 6

and

page 7

. Mounting/

drilling recommendations are provided on

page 39

and

page 40

.

The PE termination point must be connected to an external ground at the
installation site according to local regulations. Connect a grounding cable from
the drive assembly to a grounding location shown in

Figure 7

. Grounding cable

must be copper.

Common DC input kits are not compliant with EN 61800-5-1.

Figure 7 - Drive Grounding

PE

PE

PE

PE

PE

PE

PE

Grounding Location for

Bottom Cable Entry

(Inverter Termination Kit)

Grounding Location for

Top Cable Entry

(Converter Termination Kit)

to Motor

Incoming Ground

to Motor

Incoming Ground

The Inverter (DC Bus) Termination

Kit connects to the Inverter (AC

Output) Termination Kit

Ground
Bond Strap

M6
5.1 N•m (45 lb•in)

M10
22.6 N•m (200 lb•in)

Ground
Bond Strap

M10
22.6 N•m (200 lb•in)

Grounding Location for

Bottom Cable Entry

(Inverter Termination Kit)

to Motor

Incoming Ground

The DC Input for Common Bus

Precharge Termination Kit

connects to the Inverter (AC

Output) Termination Kit

M6
5.1 N•m (45 lb•in)

M10
22.6 N•m (200 lb•in)

Ground
Bond Strap

AC Input

Common DC Input