Rockwell Automation 20G PowerFlex 755 IP00 NEMA/UL Open Drive - Frames 8-10 User Manual

Page 25

Advertising
background image

Rockwell Automation Publication 750-IN020C-EN-P - May 2012

25

PowerFlex 755 IP00, NEMA/UL Open Type Drive

All control (I/O) and signal wiring to the drive must use cable with a
braided shield providing 75% or greater coverage, or the cables must be
housed in metal conduit, or equivalent shielding must be provided. When
shielded cable is used, only the drive end of the cable shield should be
terminated with a low-impedance connection to earth. The cable shield
may be terminated either by using a shielded connector in conjunction
with a conduit plate or conduit box, or the shield may be clamped to an
“EMC plate.”

Motor cabling must be separated from control and signal wiring wherever
possible.

Maximum motor cable length must not exceed the maximum length
indicated in

Table 1

for compliance with radio frequency emission limits

for the specific standard and installation environment.

EMC cores must be applied to input power and motor cabling for some
models of the PowerFlex 750-Series drives as indicated in

Table 1

.

The drive must be powered from an earthed supply system such as a TN or
TT system and the PE-A and PE-B jumpers in the drive must be installed.
Refer to Drive Power Jumper Configuration in the PowerFlex 750-Series
Installation Instructions, publication 750-IN001.

IP00 and NEMA/UL Open Type drives must be installed in suitable
supplementary EMC enclosures to achieve compliance with EN 61800-3.

Table 1 - PowerFlex 750-Series RF Emission Compliance and Installation Requirements

Drive Frame
Catalog Number

Standard / Limits

EN61800-3 Category C1
EN61000-6-3
CISPR11 Group 1 Class B

EN61800-3 Category C2
EN61000-6-4
CISPR11 Group 1 Class A
(input power

20 kVA)

EN61800-3 Category C3
(I

100 A)

CISPR11 Group 1 Class A
(Input power > 20 kVA)

EN61800-3 Category C3
I > 100 A

Frame 8 - AC Input

Compliance possible with
supplementary mitigation
(Consult factory)

Compliance possible with
supplementary mitigation
(Consult factory)

30 m motor cable limit

(1)

with output core.

(2)

30 m motor cable limit

(1)

with

output core.

(2)

Frame 9 - AC Input

Compliance possible with
supplementary mitigation
(Consult factory)

Compliance possible with
supplementary mitigation
(Consult factory)

30 m motor cable limit

(1)

with output core

(2)

and input

core.

(3)

30 m motor cable limit

(1)

with

output core

(2)

and input core.

(3)

Frame 10 - AC Input

Compliance possible with
supplementary mitigation
(Consult factory)

Compliance possible with
supplementary mitigation
(Consult factory)

30 m motor cable limit

(1)

with output core

(2)

and input

core.

(3)

Door shielding kit

installed.

30 m motor cable limit

(1)

with

output core

(2)

and input core.

(3)

Door shielding kit installed.

Frames 8…9 - Common DC Input

Compliance possible with
supplementary mitigation
(Consult factory)

Compliance possible with
supplementary mitigation
(Consult factory)

30 m motor cable limit

(1)

with output core

(2)

and input

core.

(4)

30 m motor cable limit

(1)

with

output core

(2)

and input core.

(4)

Frame 10 - Common DC Input

Compliance possible with
supplementary mitigation
(Consult factory)

Compliance possible with
supplementary mitigation
(Consult factory)

30 m motor cable limit

(1)

with output core

(2)

and input

core.

(4)

Door shielding kit

installed.

30 m motor cable limit

(1)

with

output core

(2)

and input core.

(3)

Door shielding kit installed.

More Stringent Limits

Less Stringent Limits

(1) Intended to be powered from an industrial power network supplied by a dedicated power transformer or generator and not from LV power lines supplying other customers.
(2) EMC kit number 20-750-EMCCM1-F8. Kit contains one core. Each drive assembly requires one EMC kit. Order one kit for a Frame 8 drive, two kits for a Frame 9 drive, three

kits for a Frame 10 drive.

(3) EMC kit number 20-750-EMCCM1-F9. Kit contains one core. Each drive assembly requires one EMC kit. Order two kits for a Frame 9 drive, three kits for a Frame 10 drive.
(4) EMC kit number 20-750-CBPEMCCM1-F8 is included with the termination kit.

Advertising