Rockwell Automation Publication 750-IN020C-EN-P - May 2012

PowerFlex 755 IP00, NEMA/UL Open Type Drive

Cable Routing

Control Pod Cable Routing

Supports, clips, and cable ties are provided to help route and secure cabling inside
the Control Pod.

Figure 20 - Frame 8 Control POD Detail

IMPORTANT

When routing cabling into the control Pod, do not block the cooling fan

outlet.

Do not ground shield wires to inner sheet metal bucket supporting option

modules.

No.

Description

I/O signal cable shield termination points. Use M4 screws and ring terminals provided to tie together and
terminate drain wires and shields.

Ground shield wires to outer sheet metal bucket. Strip cable insulation 25 mm (1 in.) to expose braid. Attach cable
ties around shield and through slots. Pull tight.

Attachment points for cable management devices provided (6 places).

Cable support ladder.

Fan outlet. Keep clear to help ensure proper cooling.

Control cable entry and routing.

Human Interface Module (HIM) cable entry and routing.

Shield termination points.

Inverter Fiber-optic connection

Internal 24V power connection