16

Rockwell Automation Publication 750-IN020C-EN-P - May 2012

PowerFlex 755 IP00, NEMA/UL Open Type Drive

Installation Tools

This list covers the tools needed for drive installation.

Enclosure Requirements

The following specifications must be met for proper installation.

Bus Bars

Power wiring is connected to the drive power terminals (see

page 47

) using the

Field Termination kits shown on

page 6

and

page 7

or fabricated using material

with the following specifications:

Material: CDA 110 Copper

Minimum Cross Section: 80.7mm

2

(0.125

in.

2

) per each 100 A of drive

rating.

IMPORTANT

Care must be taken to ensure that tools and/or hardware components do not fall into
open drive assemblies. Do not energize the drive unless all loose tools and/or hardware
components have been removed from the drive assemblies and enclosure.

Tool Description

Details

ESD-protected place of work

Working surface, Floor covering, seat and ground connections

ESD-protective clothing

Wrist wrap, shoes, overall clothing (coat)

Allen socket wrench

5 mm

Allen socket wrench extension

254 mm (10 in.)

Flat nose screw driver

5 mm (0.19 in.), 6.4 mm (0.25 in.), 9.5 mm (0.375 in.), #1, #2

Hexalobular screw driver/bit

#15, #20, #25, #40, #45

Hexagonal socket wrench

7 mm, 8 mm, 10 mm, 12 mm, 13 mm, 17 mm, 18 mm

Combination wrench

10 mm, 17 mm

Phillips® screw driver/bit

(1)

(1) Phillips and Pozidriv are registered trademarks of the Phillips Screw Company.

#2, 492-C

Pozidriv®

(1)

#2

Torque wrench

1...12 N•m (8.8…106 lb•in)

Torque wrench

6...50 N•m (53…443 lb•in)

Roll-out cart

20-750-CART1-F8
Note: The roll-out cart is required to remove the drive assembly from the
enclosure.

Frame 8

Frame 9

Frame 10

Width

800 mm (31.5 in.) min.

1600 mm (63.0 in.) min.

2400 mm (94.5 in.) min.

Depth

600 mm (23.6 in.) min.

Height

2200 mm (86.6 in.) min.

Weight

Enclosure must be able to support the total equipment weight stated on

page 36

.

Construction

According to EN60439-1

ATTENTION: To guard against drive damage, DO NOT connect power wires
directly to the drive power terminals. Power wiring must be connected to bus
bars which are fastened to the drive power terminals.

Advertising