Figure 6 – Rockwell Automation 20G PowerFlex 755 IP00 NEMA/UL Open Drive - Frames 8-10 User Manual

Page 21

Advertising
background image

Rockwell Automation Publication 750-IN020C-EN-P - May 2012

21

PowerFlex 755 IP00, NEMA/UL Open Type Drive

Figure 6 - Terminal Block for Enclosure Fans - TB2

TB2 Terminal Designations

ATTENTION: To avoid an electric shock hazard when servicing the drive, a
means for Lockout/Tagout of an external 120/240V power source must be
provided. Locking and tagging the common bus precharge disconnect switch
alone does not provide sufficient protection when servicing the drive.

TB2

1

2

3

4

TB2

1
2
3
4
5

6

Flat
0.5 N•m (4.5 lb•in)

Flat
0.5 N•m (4.5 lb•in)

=

AC Input Drive

Common DC Input Drive

Drive

Terminal

Name

Description

Strip Length

AC Input
Drive

1

Shunt Trip Com.

Do Not Use

2

Shunt Trip N.O.

3

Fan

240V AC, 240 VA for enclosure fans

7.0 ±0.5 mm (0.28
±0.02 in.)

4

Fan

Common DC
Input Drive

1

120V UPS Control
Power Input

Do Not Use

2

3

120/240V Control
Power Input

Control Power (user supplied) - 120/
240V AC, 50/60 Hz, 8.3/4.2 A, 1 kVA

7.0 ±0.5 mm (0.28
±0.02 in.)

(1)

(1) Refer to page

59

for control and I/O wire recommendations.

4

5

Fan

240V AC, 240 VA for enclosure fans

7.0 ±0.5 mm (0.28
±0.02 in.)

(2)

(2) Refer to page

20

for wire recommendations.

6

Fan

Advertising