Rockwell Automation Publication 750-IN020C-EN-P - May 2012

PowerFlex 755 IP00, NEMA/UL Open Type Drive

Figure 1 - Dual Airflow System

Figure 2 - Intake Duct Details

Ventilation Requirements

No.

Free Area

Description

780 cm

2

(120.9 in.

2

)

Enclosure
Cooling

Enclosure Fans

(1)

(1) Enclosure fans are required and must meet or exceed the

performance shown in

Figure 5

. In addition, the fans should be

mounted as high as possible on the door and aligned with the
front of the drive assembly.

See Important statement below

Drive Power
Cooling

811.6 cm

2

(125.8 in.

2

)

Enclosure Cooling

Drive Power Cooling

Shown with optional hood and inlet filter.

IMPORTANT

For vertical mounting applications a duct section must be fabricated to fit
between the gasket on the drive and the inside of the enclosure door.
Depending on the enclosure used, the drive mounting location in the enclosure
(set-back) can range between 12.7…54.5 mm (0.50…2.13 in.). To assure
sufficient Control Pod access, the maximum set-back of the drive behind the
door is 54.5 mm (2.13 in.). The duct must contact and slightly compress the
gasket to seal the drive power cooling air from the enclosure cooling air.
Reference the dimensions provided in

Figure 2

.

410.5

(16.16)

451.0

(17.75)

114.3

(4.50)

87.2

(3.43)

46.7

(1.84)

45

°

Duct must contact gasket

when door is closed

Gasket

Duct
(User Supplied)

Upper Vent

Filter not shown for clarity