Selecting/verifying control transformer voltage – Rockwell Automation 20G PowerFlex 755 IP00 NEMA/UL Open Drive - Frames 8-10 User Manual

Page 41

Advertising
background image

Rockwell Automation Publication 750-IN020C-EN-P - May 2012

41

PowerFlex 755 IP00, NEMA/UL Open Type Drive

Selecting/Verifying Control
Transformer Voltage

The control transformer is located inside the upper right part of the drive
assembly and is typically set to match the input line voltage. The control
transformer provides the single-phase 240V internal control voltage, power for
the drive blower, and the enclosure fans. If the line voltage is different than the
voltage class specified on the drive nameplate, it may be necessary to change
transformer taps. To gain access to the transformer, refer to the PowerFlex 750-
Series Hardware Service Manual, publication 750-TG001.

50/60 Hz

H1

H2

H3

H4

H5

X2

X1

240V

380 / 415V

440 / 480V

575 / 600V

690V

50/60 Hz

H1

H2

H3

X2

X3

X1

120V

240V

240V

120V

P2
1.8 N•m (16 lb•in)

AC Input Drive

Common DC Input Drive