Catalog number explanation – Rockwell Automation 20G PowerFlex 755 IP00 NEMA/UL Open Drive - Frames 8-10 User Manual

Page 5

Advertising
background image

Rockwell Automation Publication 750-IN020C-EN-P - May 2012

5

PowerFlex 755 IP00, NEMA/UL Open Type Drive

Catalog Number Explanation

Position

1…3

4

5

6

7

8…10

11

12

13

14

15

16

17

18

20G

1

1

T

D

485

A

N

0

N

N

N

N

N

a

b

c

d

e

f1…f2

g

h

a

Drive

Code

Type

20G

PowerFlex 755

b

Future Use

c

Input Type

Code

Description

1

AC Input w/Precharge

4

DC Input w/Precharge

d

Enclosure

Code

Description

T

IP00, UL Open Type without Control POD

e

Voltage Rating

Code

Voltage

C

400V AC / 540V DC

D

480V AC / 650V DC

E

600V AC / 810V DC

F

690V AC / 932V DC (not UL listed)

f1

ND Rating

400V AC / 540V DC, 50 Hz Input

Code

Amps

kW

Quantity

Required

Equivalent

Frame Size

C460

460

250

1

8

C540

540

315

1

C567

567

315

1

C650

650

355

1

C750

750

400

1

C770

770

400

1

C460

910

500

2

9

C540

1040

560

2

C567

1090

630

2

C650

1175

710

2

C750

1465

800

2

C770

1480

850

2

C567

1590

900

3

10

C770

2150

1250

3

To achieve the extended ratings listed for Frames 9 and 10, the base
Frame 8 drive must be paralleled 2 or 3 times. Refer to the Drive
Rating tables on pages 8, 9, 12, and 13 for detailed information.

f2

ND Rating

480V AC / 650V DC, 60 Hz Input

Code

Amps

Hp

Quantity

Required

Equivalent

Frame Size

D430

430

350

1

8

D485

485

400

1

D545

545

450

1

D617

617

500

1

D710

710

600

1

D740

740

650

1

D430

800

700

2

9

D485

960

800

2

D545

1045

900

2

D617

1135

1000

2

D710

1365

1100

2

D740

1420

1250

2

D545

1525

1350

3

10

D740

2070

1750

3

To achieve the extended ratings listed for Frames 9 and 10, the base
Frame 8 drive must be paralleled 2 or 3 times. Refer to the Drive
Rating tables on pages 8, 9, 12, and 13 for detailed information.

f3

ND Rating

600V AC / 810V DC, 60 Hz Input

Code

Amps

Hp

Quantity

Required

Equivalent

Frame Size

E295

295

300

1

8

E355

355

350

1

E395

395

400

1

E435

435

450

1

E460

460

500

1

E510

510

500

1

E295

595

600

2

9

E355

630

700

2

E395

760

800

2

E435

825

900

2

E460

900

950

2

E510

980

1000

2

E395

1110

1100

3

10

E510

1430

1400

3

To achieve the extended ratings listed for Frames 9 and 10, the base
Frame 8 drive must be paralleled 2 or 3 times. Refer to the Drive
Rating tables on pages 8, 9, 12, and 13 for detailed information.

f4

ND Rating

690V AC / 932V DC, 60 Hz Input (not UL listed)

Code

Amps

kW

Quantity

Required

Equivalent

Frame Size

F265

265

250

1

8

F330

330

315

1

F370

370

355

1

F415

415

400

1

F460

460

450

1

F500

500

500

1

F265

590

560

2

9

F330

650

630

2

F370

710

710

2

F415

765

750

2

F460

795

800

2

F500

960

900

2

F370

1040

1000

3

10

F500

1400

1400

3

To achieve the extended ratings listed for Frames 9 and 10, the base
Frame 8 drive must be paralleled 2 or 3 times. Refer to the Drive
Rating tables on pages 8, 9, 12, and 13 for detailed information.

g

Filtering and CM Cap Configuration

Code

Filtering

Default CM Cap Connection

A

Yes

Jumper Removed

J

Yes

Jumper Installed

480V drives must select code "A." Jumpers are included for field
reconfiguration as desired.

h

Dynamic Braking

§

Code

Internal Resistor

Internal Transistor

N

No

No

§

Not available on Frames 8…10.