Rockwell Automation Publication 750-IN020C-EN-P - May 2012

47

PowerFlex 755 IP00, NEMA/UL Open Type Drive

Power Terminals

For easier power wiring, movable L-bracket assemblies are included with the
Field Termination kits to connect the AC line input, output to the motor, and
DC bus power. Arrange the moveable L-brackets and secure using the torque
guidelines listed. Refer to pages

49

57

for kit installation guidelines and

page 39

or

page 40

for recommended mounting locations and dimensions.

ATTENTION: To guard against drive damage, Do Not connect power wires
directly to the drive power terminals. Power wiring must be connected to bus
bars which are fastened to the drive power terminals. Refer to

page 16

.

W/T3

V/T2

U/T1

-DC

+DC

T/L3

S/L2

R/L1

TESTPOINTS

DC-

DC+

TESTPOINTS

DC-

DC+

Inverter/Converter

Assembly Shown

Do Not connect field

wiring directly to power

terminals

Bus Bar to Power

Terminal Detail

M10 x 35 mm SEMS

Torque: 22.4 N•m

(200 lb•in)