Under reverse setpoint – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, PRIOR to Firmware rev. 3.0 User Manual
Page 118

Publication 1404-UM001D-EN-E - October 2004
5-4 Setpoint Programming and Operation
Figure 5.3 Under Forward Setpoint Operation
Under Reverse Setpoint
An under reverse setpoint is the mirror image of an under forward
setpoint. The magnitude and all limits are negative numbers.
An under reverse setpoint activates when the magnitude of the
parameter being monitored (defined by the Setpoint Type) decreases
below the Setpoint Low Limit in the negative direction and remains
below the limit for a time greater than the Setpoint Action Delay. The
setpoint releases when the magnitude of the parameter being
monitored increases above the Setpoint High Limit and stays above
the limit for a time greater than the Setpoint Release Delay.
Figure 5.4 Under Reverse Setpoint Operation
Parameter Value
Setpoint High Limit
Setpoint Low Limit
Setpoint Activated
≥Setpoint Action Delay
<Setpoint
Release Delay
≥Setpoint
Release Delay
Time (s)
0
Setpoint Deactivated
Maximum Excursion
Parameter Value (-)
Setpoint High Limit
Setpoint Low Limit
Setpoint Activated
≥Setpoint Action Delay
<Setpoint
Release Delay
≥Setpoint
Release Delay
Time (s)
0
Setpoint Deactivated
Maximum Excursion