Publication 1404-UM001D-EN-E - October 2004

5-4 Setpoint Programming and Operation

Figure 5.3 Under Forward Setpoint Operation

Under Reverse Setpoint

An under reverse setpoint is the mirror image of an under forward
setpoint. The magnitude and all limits are negative numbers.

An under reverse setpoint activates when the magnitude of the
parameter being monitored (defined by the Setpoint Type) decreases
below the Setpoint Low Limit in the negative direction and remains
below the limit for a time greater than the Setpoint Action Delay. The
setpoint releases when the magnitude of the parameter being
monitored increases above the Setpoint High Limit and stays above
the limit for a time greater than the Setpoint Release Delay.

Figure 5.4 Under Reverse Setpoint Operation

Parameter Value

Setpoint High Limit

Setpoint Low Limit

Setpoint Activated

≥Setpoint Action Delay

<Setpoint
Release Delay

≥Setpoint
Release Delay

Time (s)

0

Setpoint Deactivated

Maximum Excursion

Parameter Value (-)

Setpoint High Limit

Setpoint Low Limit

Setpoint Activated

≥Setpoint Action Delay

<Setpoint
Release Delay

≥Setpoint
Release Delay

Time (s)

0

Setpoint Deactivated

Maximum Excursion