Ee table a.23), Table a.23 t, Table a.23 co – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, PRIOR to Firmware rev. 3.0 User Manual
Page 207: Min/max log configuration/read-back select, Table a.23

Publication 1404-UM001D-EN-E - October 2004
Powermonitor 3000 Data Tables A-33
Table A.23 Min/Max Log Configuration/Read-Back Select
CSP File No.
N26
Remote I/O BT
13
CIP Assy. Inst.
29 (Write), 30 (Read)
No. of Elements
9
User Configurable No
Data Type
Integer
Data Access
Read / Write
PM3000 Type
All
Element
No.
Modbus
Address
Element name
Range
Default
Value
Comment
0
40901
Password
0 to 9999
0
Required for configuration, -1 for readback
select, returns -1.
1
40902
Min/max parameter to read
0 to 73
1
Refer to Interfacing with the Min/Max Log
Using Communications on page 7-14
2
40903
Read-back mode
0 to 1
0
3
40904
Enable/disable Min/max log
0 to 1
1
4
40905
Clear min/max log
0 to 1
0
5
40906
Timestamp of last min/max clear; year
month/day
hour/minute
second/hsec
1998 to 2097
-
6
40907
0101 to 1231
-
7
40908
0000 to 2359
-
8
40909
0000 to 5999
-