Time of use records – reactive energy and demand, Table a.57 – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, PRIOR to Firmware rev. 3.0 User Manual
Page 241

Publication 1404-UM001D-EN-E - October 2004
Powermonitor 3000 Data Tables A-67
Element
No.
Modbus
Address
Element name
Range
Units
Comment
0
32301-02
Off-peak real energy
-999,999.0 to
999,999.0
MWh
Refer to Reading Time-of-Use Log Data on
page 7-18
1
32303-04
Off-peak real energy
-999.999.999 to
999.999.999
kWh
2
32305-06
Off-peak demand
0.0 to 999.9 x 10
21
Watts
3
32307-08
Mid-peak real energy
-999,999.0 to
999,999.0
MWh
4
32309-10
Mid-peak real energy
-999.999.999 to
999.999.999
kWh
5
32311-12
Mid-peak demand
0.0 to 999.9 x 10
21
Watts
6
32313-14
Peak real energy
-999,999.0 to
999,999.0
MWh
7
32315-16
Peak real energy
-999.999.999 to
999.999.999
kWh
8
32317-18
Peak demand
0.0 to 999.9 x 10
21
Watts
9
32319-20
Start date
000101 to 991231
YYMMDD
Start month / day for data stored in this
record, inclusive
10
32321-22
End date
000101 to 991231
YYMMDD
End month / day for data stored in this
record, inclusive
11
33323-24
Record number
0 to 12
Table A.57 Time of Use Records – Reactive Energy and Demand
CSP File No.
F57
Remote I/O BT
52
CIP Assy. Inst.
73
No. of Elements
12
User Configurable No
Data Type
Floating point
Data Access
Read only
PM3000 Type
All