Table a.34. th, Table a.34, Reads of table a.34 will – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, PRIOR to Firmware rev. 3.0 User Manual
Page 218: Harmonic results; thd, crest factor, and more

Publication 1404-UM001D-EN-E - October 2004
A-44 Powermonitor 3000 Data Tables
Table A.34 Harmonic Results; THD, Crest Factor, and More
CSP File No.
F34
Remote I/O BT
23
CIP Assy. Inst.
41
No. of Elements
9 (M4, M5); 10 (M6, M8)
User Configurable No
Data Type
Floating Point
Data Access
Read only
PM3000 Type
See table
Element
No.
Modbus
Address
M4
M5
M
6
M
8
Element name
Range
Comment
0
31201-02
•
• • Channel number
1 to 9
Refer to Reading Harmonic Analysis Data on page 8-11
1
31203-04
•
• • % IEEE THD
0.0 to 1000.0
2
31205-06
•
• • % IEC thd (DIN)
0.0 to 1000.0
3
31207-08
•
• • Crest Factor
0.0 to 10.0
4
31209-10
•
• • THD & Crest iteration 0 to 32767
5
31211-12
•
Reserved
0
• • TIF
0.0 to 999.9x10
22
6
31213-14
•
Reserved
0
• • K-Factor
0.0 to 999.9x10
22
7
31215-16
•
Reserved
0
• • IEEE-519 TDD
0.0 to 999.9x10
22
8
31217-18
•
Reserved
0
• • IEEE-519 Pass/Fail
-1 to 1
9
31219-20
•
Reserved
0
• • FFT iteration
0 to 32767