Table A.46 Transient Capture Results
CSP File No.
N46
Remote I/O BT
60
CIP Assy. Inst.
57
No. of Elements
29 (DeviceNet only); 59 (All other communications types)
User Configurable No
Data Type
Integer
Data Access
Read only
PM3000 Type
M8 only
Element
No.
Modbus
Address
Element name
Range
Comment
0
-
Timestamp;
Month/day
Hour/minute
Second/hsec
0000 to 1231
Capture trigger timestamp, see page 4-18.
1
-
0000 to 2359
2
-
0000 to 5999
3
-
Capture #
1 to 6
Refer to Reading Transient Capture Data on page 8-21.
4
-
Channel number
1 to 7
5
-
Block number
6
-
Reserved
0
7
-
Unique Transient Capture ID
0 to 30000
8
-
Reserved
0
9
-
Data Point 1
-8192 to 8191
10
-
Data Point 2
11
-
Data Point 3
12
-
Data Point 4
13
-
Data Point 5
14
-
Data Point 6
15
-
Data Point 7
16
-
Data Point 8
17
-
Data Point 9
18
-
Data Point 10
19
-
Data Point 11
20
-
Data Point 12
21
-
Data Point 13
22
-
Data Point 14
23
-
Data Point 15
24
-
Data Point 16
25
-
Data Point 17
26
-
Data Point 18
27
-
Data Point 19
28
-
Data Point 20