Table a.45, Table a.45 specif, Transient capture clear/read-back data select – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, PRIOR to Firmware rev. 3.0 User Manual
Page 230

Publication 1404-UM001D-EN-E - October 2004
A-56 Powermonitor 3000 Data Tables
Table A.45 Transient Capture Clear/Read-Back Data Select
CSP File No.
N45
Remote I/O BT
17
CIP Assy. Inst.
55 (Write), 56 (Read)
No. of Elements
13
User Configurable No
Data Type
Integer
Data Access
Read / Write
PM3000 Type
M8 only
Applies to:
Table 45: Transient capture results
Element
No.
Modbus
Address
Element name
Range
Default
Value
Comment
0
-
Password
0 to 9999
0
Required for configuration, -1 for readback select, returns
-1.
1
-
Dnet unique write
identifier
-32768 to 32767
0
Refer to DeviceNet Unique Write Identifier on page 4-36.
2
-
Capture number
0 to 6
1
Refer to Reading Transient Capture Data on page 8-21.
3
-
Channel number
1 to 7
1
4
-
Block number
See page 90
1
5
-
Read-back mode
0 to 2
0
6
-
Clear command
0 to 3
0
7
-
Reserved
0
0
8
-
Reserved
0
0
9
-
Reserved
0
0
10
-
Capture clear status
0 to 63
-
11
-
Capture ready status
0 to 63
-
12
-
Reserved
0
0