Table A.9 Metering Voltage, Current and Frequency Result
CSP File No.
F15
Remote I/O BT
38
CIP Assy. Inst.
14
No. of Elements
14
User Configurable No
Data Type
Floating point
Data Access
Read only
PM3000 Type
All
Element
No.
Modbus
Address
Element name
Units
Range
Comment
0
30101-2
L1 Current
Amps (A)
0.0 to 999.9x10
21
Refer to Voltage, Current and Frequency Results on
page 3-4.
1
30103-4
L2 Current
0.0 to 999.9x10
21
2
30105-6
L3 Current
0.0 to 999.9x10
21
3
30107-8
Avg. Current
0.0 to 999.9x10
21
4
30109-10
L1-N Voltage
Volts (V)
0.0 to 999.9x10
21
5
30111-12
L2-N Voltage
0.0 to 999.9x10
21
6
30113-14
L3-N Voltage
0.0 to 999.9x10
21
7
30115-16
Avg. L-N Voltage
0.0 to 999.9x10
21
8
30117-18
L1-L2 Voltage
0.0 to 999.9x10
21
9
30119-20
L2-L3 Voltage
0.0 to 999.9x10
21
10
30121-22
L3-L1 Voltage
0.0 to 999.9x10
21
11
30123-24
Avg L-L Voltage
0.0 to 999.9x10
21
12
30125-26
Frequency, last cycle
Hertz (Hz) 40.0 to 75.0
Returns 0 or 999.0 if out of range
13
30127-28
Metering iteration
-
0 to 32767
Increments by 1 to 32767, rolls over to 0