Metering reactive energy and amp-hour results, Table a.15 – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, PRIOR to Firmware rev. 3.0 User Manual
Page 197

Publication 1404-UM001D-EN-E - October 2004
Powermonitor 3000 Data Tables A-23
Table A.15 Metering Reactive Energy and Amp-Hour Results
CSP File No.
N21
Remote I/O BT
30
CIP Assy. Inst.
21 (Write), 22 (Read)
No. of Elements
23
User Configurable No
Data Type
Integer
Data Access
Read/Write
PM3000 Type
All
Element
No.
Modbus
Address
Element name
Range
Units
Default
Value
Comment
0
40601
Password
0 to 9999
-
0
Required to clear or preset energy counters.
Returns -1.
1
40602
Parameter select
0 to 7
-
Refer to How to Clear or Preset Energy
Counters Using Communications on
page 4-52.
2
40603
KVARh forward
### x 10
9
### x 10
6
### x 10
3
### x 10
0
### x 10
-3
-999 to 999
kVARh
3
40604
4
40605
5
40606
6
40607
7
40608
KVARh reverse
### x 10
9
### x 10
6
### x 10
3
### x 10
0
### x 10
-3
-999 to 999
8
40609
9
40610
10
40611
11
40612
12
40613
KVARh net
### x 10
9
### x 10
6
### x 10
3
### x 10
0
### x 10
-3
-999 to 999
13
40614
14
40615
15
40616
16
40617
17
40618
KAh
### x 10
9
### x 10
6
### x 10
3
### x 10
0
### x 10
-3
-999 to 999
kAh
18
40619
19
40620
20
40621
21
40622
22
40623
Metering iteration
0 to 32767
-
Increments by 1 to 32767, rolls over to 0