Table a.43), Transient analysis configuration/read-back select, Table a.43 – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, PRIOR to Firmware rev. 3.0 User Manual
Page 228

Publication 1404-UM001D-EN-E - October 2004
A-54 Powermonitor 3000 Data Tables
Table A.43 Transient Analysis Configuration/Read-Back Select
CSP File No.
F43
Remote I/O BT
44
CIP Assy. Inst.
52 (Write), 53 (Read)
No. of Elements
10
User Configurable No
Data Type
Floating Point
Data Access
Read / Write
PM3000 Type
M8 only
Applies to:
Table 43: Transient analysis metering results
Element
No.
Modbus
Address
Element name
Range
Default
Value
Comment
0
-
Password
0 to 9999
0
Required for configuration, -1 for readback select,
returns -1.
1
-
DeviceNet unique write
identifier
-32768 to 32767
0
Refer to DeviceNet Unique Write Identifier on
page 4-36.
2
-
Capture #
0 to 6
1
Refer to Transient Analysis Configuration on
page 8-19.
3
-
Cycle #
1 to 12
1
4
-
Read-back mode
0 to 1
0
5
-
Detection mode
0 to 3
1
6
-
Reserved
0
0
7
-
Auto-threshold set command
0 to 1
0
8
-
Auto-threshold set duration
1 to 3600
10
9
-
Auto-threshold set margin
1.0 to 100.0
20.0
10
-
Voltage trigger threshold
0.1 to 100.0
10.0
11
-
Current trigger threshold
0.1 to 100.0
10.0
12
-
Auto-threshold duration time
left
0
0