Time of use register configuration, Table a.55, Time of use records – real energy and demand – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, PRIOR to Firmware rev. 3.0 User Manual
Page 240: Table a.56

Publication 1404-UM001D-EN-E - October 2004
A-66 Powermonitor 3000 Data Tables
Table A.55 Time of Use Register Configuration
CSP File No.
N55
Remote I/O BT
49
CIP Assy. Inst.
70 (Write), 71 (Read)
No. of Elements
10
User Configurable No
Data Type
Integer
Data Access
Read / Write
PM3000 Type
All
Element
No.
Modbus
Address
Element name
Range
Default
Comment
0
42201
Password
-1 to 9999
0
Required for configuration, -1 for readback select,
Returns -1
1
42202
Record to read back
0 to 12
0
Refer to Configuring the Time-of-Use Log on page 7-17
2
42203
Reserved
0
0
3
42204
Write command
0 to 1
0
4
42205
Log day
1 to 31
31
5
42206
Off peak day
0 to 127
65
6
42207
Mid peak a.m.
0 to 4095
1792
7
42208
Mid peak p.m.
120
8
42209
Peak a.m.
2048
9
42210
Peak p.m.
7
Table A.56 Time of Use Records – Real Energy and Demand
CSP File No.
F56
Remote I/O BT
51
CIP Assy. Inst.
72
No. of Elements
12
User Configurable No
Data Type
Floating point
Data Access
Read only
PM3000 Type
All