Transient analysis metering results, Table a.44 – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, PRIOR to Firmware rev. 3.0 User Manual
Page 229

Publication 1404-UM001D-EN-E - October 2004
Powermonitor 3000 Data Tables A-55
Table A.44 Transient Analysis Metering Results
CSP File No.
F44
Remote I/O BT
32
CIP Assy. Inst.
54
No. of Elements
14
User Configurable No
Data Type
Floating Point
Data Access
Read only
PM3000 Type
M8 only
Element
No.
Modbus
Address
Element name
Range
Comment
0
-
Capture number
1 to 6
Refer to Reading Transient Analysis Metering Data on
page 8-20.
1
-
Cycle number
1 to 12
2
-
L1-L2 or L1-N Voltage
0.0 to 999.9x10
21
3
-
L2-L3 or L2-N Voltage
0.0 to 999.9x10
21
4
-
L3-L1 or L3-N Voltage
0.0 to 999.9x10
21
5
-
L1 Current
0.0 to 999.9x10
21
6
-
L2 Current
0.0 to 999.9x10
21
7
-
L3 Current
0.0 to 999.9x10
21
8
-
L4 Current
0.0 to 999.9x10
21
9
-
Voltage Index at trigger
-999.0x10
3
to 999.0x10
3
10
-
Current Index at trigger
-999.0x10
3
to 999.0x10
3
11
-
Voltage Trigger Threshold
0.0 to 999.0x10
3
12
-
Current Trigger Threshold
0.0 to 999.0x10
3
13
-
Unique Transient Capture ID
0 to 30000