Instance attributes, Semantics, Instance attributes semantics – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, PRIOR to Firmware rev. 3.0 User Manual
Page 318

Publication 1404-UM001D-EN-E - October 2004
F-12 Powermonitor 3000 EtherNet/IP Device Profile
Instance Attributes
Semantics
The NVS Object’s attributes are defined as follows:
Revision - The current major and minor revision of the NVS Object
itself.
Status - The status attribute reports the current status of the NVS
Object instance. The Status can be any one of the following:
Instance Revision - The current major and minor revision of
firmware or data represented by this instance of the NVS Object.
Table F.23
Attr ID
Acces
s
Name
Data Type
Default
Value
1
Get
Status
UINT
2
Get
Revision
UINT
1
Table F.24
Value
Description
0
Nothing new / No Update
1
Success on Transfer
2
Success on Programming
3
Failure on Transfer
4
Failure on Programming
5
Faulted
TIP
The DC's web content flash file does not utilize
revision levels. Consequently, instance 2 of the NVS
Object always reports a major / minor revision of 1.0.