Harmonic analysis configuration/read-back select, Table a.33 – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, PRIOR to Firmware rev. 3.0 User Manual
Page 217

Publication 1404-UM001D-EN-E - October 2004
Powermonitor 3000 Data Tables A-43
Table A.33 Harmonic Analysis Configuration/Read-Back Select
CSP File No.
N33
Remote I/O BT
14
CIP Assy. Inst.
39 (Write), 40 (Read)
No. of Elements
9
User Configurable No
Data Type
Integer
Data Access
Read /Write
PM3000 Type
See table
Applies to:
Table A.34 (All models)
Table A.35,Table A.36, Table A.37, Table A.38 (M6 & M8)
Table A.48, Table A.49 (M8 only)
Element
No.
Modbus
Address
M4
M5
M
6
M
8
Element name
Range
Default
Value
Comment
0
41201
•
• • Password
0 to 9999
0
Required for configuration, -1 for readback
select, returns -1.
1
41202
•
• • Channel
1 to 9
1
Refer to Configuring Harmonic Analysis on
page 8-10
2
41203
•
• • Read-back mode
0 to 1
0
3
41204
•
Reserved
0
0
• • Individual harmonic data type 0 to 1
0
4
41205
•
Reserved
0
0
• • Enable/disable Harmonics
0 to 1
1
5
41206
•
Reserved
0
0
• • IEEE-519 Max I
sc
Integer
0 to 9999
0
6
41207
•
Reserved
0
0
• • IEEE-519 Max I
sc
Exponent
-4 to 21
0
7
41208
•
Reserved
0
0
• • IEEE 519 Max I
dmnd
Integer
0 to 9999
0
8
41209
•
Reserved
0
0
• • IEEE 519 Max I
dmnd
Exponent
-4 to 21
0