Metering sequence voltage and current results, Table a.10 – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, PRIOR to Firmware rev. 3.0 User Manual
Page 192

Publication 1404-UM001D-EN-E - October 2004
A-18 Powermonitor 3000 Data Tables
Table A.10 Metering Sequence Voltage and Current Results
CSP File No.
F16
Remote I/O BT
27
CIP Assy. Inst.
15
No. of Elements
11
User Configurable No
Data Type
Floating point
Data Access
Read only
PM3000 Type
All
Element
No.
Modbus
Address
Element name
Units
Range
Comment
0
30201-02
L4 (Zero sequence) Current
Amps (A)
0.0 to 999.9x10
21
Refer to Symmetrical Component Analysis
Results on page 3-5.
1
30203-04
Positive Sequence Current
0.0 to 999.9x10
21
2
30205-06
Negative Sequence Current
0.0 to 999.9x10
21
3
30207-08
% Current unbalance
Per Cent
0.0 to 100.0
4
30209-10
Positive Sequence Voltage
Volts (V)
0.0 to 999.9x10
21
5
30211-12
Negative Sequence Voltage
0.0 to 999.9x10
21
6
30213-14
% Voltage unbalance
Per Cent
0.0 to 100.0
7
30215-16
Phase rotation
-
0 to 2
0 = No rotation
1 = ABC rotation
2 = ACB rotation
8
30217-18
Average frequency
Hertz (Hz)
40.0 to 75.0
Average of the last 1 or 8 cycles.
Returns 0 or 999.0 if out of range
9
30219-20
Frequency source
-
0 to 2
0 = V1, 1 = V2, 2 = V3
10
30221-22
Metering iteration
-
0 to 32767
Increments by 1 to 32767, rolls over to 0