Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, PRIOR to Firmware rev. 3.0 User Manual
Page 95

Publication 1404-UM001D-EN-E - October 2004
Communications 4-35
xxxxxx = Destination MAC ID / node no. (6-bit field)
yyyyyy = Source MAC ID / node no. (6-it field)
DeviceNet Class Services
As a group 2 slave device, the Powermonitor 3000 supports the
following class and instance services.
DeviceNet Object Classes
The Powermonitor 3000 supports the following DeviceNet object
classes:
2
10xxxxxx010
Master’s COS / Cyclic ACK message
10yyyyyy011
Slave’s explicit / unconnected response message
10xxxxxx100
Master’s explicit request message
10xxxxxx101
Master’s I/O poll command / COS / Cyclic message
10xxxxxx110
Group 2 only unconnected explicit message request
10xxxxxx111
Duplicate MAC ID check message
3
11101xxxxxx
Unconnected explicit response
11110xxxxxx
Unconnected explicit request
4
Not used
Table 4.8 DeviceNet Class Services
Service Name
Service Code
(hex)
Service Code
(decimal)
Reset
05
05
Get_Attribute_Single
0E
14
Set_Attribute_Single
10
16
Allocate_Group_2_Identifier_Set
4B
75
Release_Group_2_Identifier_Set
4C
76
Table 4.7 DeviceNet Message Types
Group
CAN Identifier
Field
Message Type