Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, PRIOR to Firmware rev. 3.0 User Manual
Page 291

Publication 1404-UM001D-EN-E - October 2004
Sample Applications C-37
Powermonitor 3000 Ladder Example for SLC through SCNR
While message is pending bring back the CIP message control status.
0000
B3:0
0
Message Pending
COP
Copy File
Source #M0:3.1000
Dest
#N7:0
Length
10
COP
After setting up N9 CIP_SETUP file, turn on bit N9:11/1 to start the read transfer from the power monitor. This process clears
out the first 9
words of N7:0 CIP message file. Copies the request from the CIP_SETUP file to N7 first 9 words. Moves a 0 to M0 scanner locat
ion
M0:3.1009 (This loacation needs to be set to 0 when requesting information.) Enable the transfer by turning bit N7:0/15 EN to
1. Copy the
request information into the request area of the M0 file offset 1000 + 9. Set the bit for Message Pending.
0001
N9:11
1
Perform Read
B3:0
0
Message Pending
FLL
Fill File
Source
0
Dest
#N7:0
Length
9
FLL
COP
Copy File
Source
#N9:0
Dest
#N7:0
Length
9
COP
MOV
Move
Source
0
0<
Dest
M0:3.1009
?<
MOV
L
N7:0
15
Enable Transfer Bit
COP
Copy File
Source
#N7:0
Dest
#M0:3.1000
Length
9
COP
L
B3:0
0
Message Pending