Untitled, Connection, Connecting the drive circuit – Rockwell Automation 937CU-AIHLP-DC1 HART Loop Converter Installation Instructions User Manual

Page 17

Advertising
background image

Connection

The following connections are available:

Terminals 10 ... 12: output I (relay 1 (change-over contact))

Terminals 16 ... 18: output II (relay 2 (change-over contact))

Terminals 7 ... 9: output III, current output as source (7/8) or sink (7/9)

Terminals 13 ... 15: output IV, current output as source (13/14) or sink (13/15)

Terminals 19 ... 21: output V, current output as source (19/20) or sink (19/21)

Terminals 22/24: connection of HART handheld

Terminals 23/24: power supply 24 VDC

10

11

I

12

16

17

II

7

mA

8+

III

13

14+

IV

250 ˜

mA

19

mA

20+

V

+

22

24-

ERR 24 V DC

Power Rail

18

9-

+

15-

+

21-

23+

24 V DC

Zone 2

Div. 2

V

-

V

-

V

-

HART

Bul. 937

C HART Loop Converter Installation Instructions

15

Connecting the Drive Circuit

1.

Connect the drive circuit to the green terminals.

2.

Note the tightening torque of the terminal screws. The tightening torque is 0.5 Nm...0.6 Nm