Defining the trip point, Defining hysteresis, Activating the restart inhibit – Rockwell Automation 937CU-AIHLP-DC1 HART Loop Converter Installation Instructions User Manual

Page 40: Defining the response delay

Advertising
background image

Bul. 937C HART Loop Converter Installation Instructions

Defining the Trip Point

1.

Enter the starting point as a floating point figure. For entering floating point figures, see

chapter 3.5.4. The defined unit from the

Unit menu is used as the

unit. See chapter 3.5.5.

2.

Confirm your entry with

OK.

Defining Hysteresis

Make sure during input that the hysteresis is at least 1 % greater than the trip point.

This avoids "fluttering" of the relay.
1.

Enter the hysteresis as a floating point figure. For entering floating point figures, see

chapter 3.5.4. The defined unit from the

Unit menu is used as the

unit. See chapter 3.5.5.

2.

Confirm your entry with

OK.

The restart inhibit is used to prevent momentary trip value violations from not being
noticed by operating personnel.

1.

Use the  or  buttons to select

On.

2.

Confirm your selection with

OK.

The relay status is retained after switching the relay.

3.

If you would like to reset the relay status, press the

ESC

or button or restart the device.

Inputting a response delay > 0 s prevents momentary trip value violations from triggering
an alarm.

1.

To change the time in steps, press the  or  buttons. Set the time from

0 s ... 250 s in increments of 5 seconds.

2.

Confirm your entry with

OK.

Activating the Restart Inhibit

The relay is reset. Exception: there is a trip value violation.

Defining the Response Delay

38

Advertising