Display Options for Current Output Values and HART Variables

To select the displayed measured values or current output values, use the  and 
buttons.

To select units for measured values, use the

Unit menu.

Every time the isolated barrier receives a HART command 3 message from the field
device, the display is updated.

The isolated barrier displays the current output values as a four-digit number. The
decimal point is set to provide the best possible resolution.

The isolated barrier shows the floating point value for HART variables as follows:

If possible, as a four-digit number with decimal point and without exponent.
Negative values are shown on the device with three digits because of the
minus sign.

A digit is rounded as necessary. For example, the number 0.3456 is shown as
0.346.

If the isolated barrier cannot show the floating point value, the mantissa and
exponent are shown in alternation.

Fault Message

The following table shows which fault message the current outputs send to the controller,

Bul. 937

C HART Loop Converter Installation Instructions

45

based on the characteristic

Setting

4 - 20 unlimited

4 - 20 NE43

down

0 mA
Cannot be distinguished from falling
below the start value

2.0 mA

up

approx. 23 mA
Cannot be distinguished from the end
value being exceeded

21.5 mA

hold

Last measured value before the fault