Bul. 937C HART Loop Converter Installation Instructions

Selecting a Mode

The device functions as primary or secondary HART master according to the
HART standard. The device is compatible with each HART handheld and for every
other HART master.

1.

Use the  or buttons to select whether the device should operate as a primary or

secondary HART master.

2.

Confirm your selection with OK.

Defining TimeOut

If the device does not receive a valid HART message within the specified
time, the communication fault fault message is output.

1.

To change the time in steps, press the  or buttons.

Set the time from 5 s ... 60 s in increments of 5 seconds.

2.

Confirm your entry with OK.

Defining ComControl

You can specify the communication type between isolated barrier and field device. The
change in communication type is effective immediately. It is not necessary to restart the
isolated barrier.
1.

Select the type of communication using the  or  buttons.

2.

Select auto detect.

If you select this type of communication, the burst configuration of the field

device is not changed.

3.

Choose polling.

If you select this type of communication, the isolated barrier deactivates the

burst configuration of the field device. The isolated barrier performs the field device
query using HART command 3.

4.

Choose burst.

If you choose this type of communication, the isolated barrier activates the

burst configuration of the field device for HART command 3.

5.

Confirm your entry with OK.