A - flexlogix system status indicators, Controller leds, Appendix a – Rockwell Automation 1794-L34 FlexLogix Controller System User Manual User Manual

Page 101: Flexlogix system status indicators, Appendix

Advertising
background image

101

Publication 1794-UM001G-EN-P - January 2007

Appendix

A

FlexLogix System Status Indicators

Controller LEDs

The table below describes the controller LEDs present on all
FlexLogix controllers.

If this indicator: is in this condition:

It means:

RUN

off

The controller is in Program or Test mode.

steady green

The controller is in Run mode.

FORCE

off

No tags contain I/O force values.
I/O forces are inactive (disabled).

steady amber

I/O forces are active (enabled).
I/O force values may or may not exist.

flashing amber

One or more input or output addresses have been forced to an On or Off state, but the
forces have not been enabled.

BAT

off

The battery supports memory.

steady red

Either the battery is:

• not installed.
• 95% discharged and should be replaced.

I/O

off

Either:

• There are no devices in the I/O configuration of the controller.
• The controller does not contain a project (controller memory is empty).

steady green

The controller is communicating with all the devices in its I/O configuration.

flashing green

One or more devices in the I/O configuration of the controller are not responding.

flashing red

The controller is not communicating to any devices.
The controller is faulted.

OK

off

No power is applied.

flashing red

One of the following:

• The controller requires a firmware update.

• A major recoverable fault occurred on the controller. To clear the fault:

1. Turn the controller keyswitch from PROG to RUN to PROG.

2. Go online with RSLogix 5000.

steady red

The controller detected a non-recoverable major fault, so it cleared the project from
memory. To recover:

1. Cycle power to the chassis.
2. Download the project.
3. Change to Run mode.

If the OK LED remains steady red, contact your Rockwell Automation representative or
local distributor.

steady green

Controller is OK.

Advertising