Publication 1794-UM001G-EN-P - January 2007

FlexLogix Back-Up on DeviceNet 105

Requirements of the Back-Up

The FlexLogix Back-Up on DeviceNet solution requires that you use
the following:

• RSLogix 5000, version 10 or higher
• 2 FlexLogix controllers, firmware revision 10.x or higher
• 2 1788-DNBO communication cards, firmware revision 2.x or

higher

Additional requirements are as follows:

• When setting up the DeviceNet network, you must set the

primary and secondary 1788-DNBO cards to the same node
address and reserve the next node address.

We recommend you set the primary and secondary 1788-DNBO
node addresses to 0 and reserve node 1. However, you can use
any successive node numbers (e.g. 30 and 31).

• All I/O and operator interfaces that required back-up must be on

DeviceNet.

• The scanlists in the two DeviceNet scanner must be identical.

IMPORTANT

Many applications use multiple communications cards in a
FlexLogix controller to communicate with several networks.
This solution requires the software and FlexLogix controllers
use version 10.x or higher.

However, if you are using the 1788-ENBT card in your
application, remember that you must use software and
FlexLogix controllers of version 11.x or higher.