Communicate over Networks 39

DH-485

For DH-485 communication, use the serial port of the controller.
However, when using a FlexLogix controller, it is recommended that
you use NetLinx networks (EtherNet/IP, ControlNet, or DeviceNet)
because excessive traffic on a DH-485 network may make it
impractical to connect to a controller with RSLogix 5000 programming
software.

The DH-485 protocol uses RS-485 half-duplex as its physical interface.
(RS-485 is a definition of electrical characteristics; it is not a protocol.)
You can configure the RS-232 port of the FlexLogix controller to act as
a DH-485 interface. By using a 1761-NET-AIC and the appropriate
RS-232 cable (1756-CP3 or 1747-CP3), a FlexLogix controller can send
and receive data on a DH-485 network.

If your application uses:

Select:

• connections to existing DH-485 networks

built-in serial port

connection from FlexLogix
controller to port 1 or port 2

FlexLogix controller

SLC 5/03 controller

1761-NET-AIC+

1747-AIC

DH-485 network

1747-CP3

or

1761-CBL-AP00

or

1747-CP3

or