Manage Controller Communications 47

Send and Receive
Messages

Messages transfer data to other devices, such as other controllers or
operator interfaces. Messages use unscheduled connections to send or
receive data. Connected messages can leave the connection open
(cache) or close the connection when the message is done
transmitting.

Connected messages are unscheduled connections on both
ControlNet and EtherNet/IP networks.

Each message uses one connection, regardless of how many devices
are in the message path. You can programmatically change the target
of a MSG instruction to optimize message transfer time.

Determine whether to cache message connections

When you configure a MSG instruction, you have the option of
whether or not to cache the connection.

See:

Logix5000 Controllers Common

Procedures Manual, 1756-PM001

Logix5000 Controllers Design

Considerations Reference Manual,

This message type:

With this
communication
method:

Is a connected
message:

The message
can be cached:

CIP data table read or write

3

3

PLC2, PLC3, PLC5, or SLC
(all types)

CIP

CIP with Source ID

DH+

3

3

CIP generic

your option

(1)

(1)

You can connect CIP generic messages. But for most applications we recommend you
leave CIP generic messages unconnected.

3

(2)

(2)

Consider caching only if the target module requires a connection.

block-transfer read or write

3

3

If the message executes

Then

repeatedly

Cache the connection.

This keeps the connection open and optimizes execution time. Opening a connection each
time the message executes increases execution time.

infrequently

Do not cache the connection.

This closes the connection upon completion of the message, which frees up that
connection for other uses.