Publication 1794-UM001G-EN-P - January 2007

84 Develop Applications

If you use the default time slice of 20%, the system overhead
interrupts the continuous task every 4 ms (of continuous task time).

If you increase the time slice to 50%, the system overhead interrupts
the continuous task every 1 ms (of continuous task time).

If the controller only contains a periodic task(s), the system overhead
timeslice value has no effect. System overhead runs whenever a
periodic task is not running.

1 ms

1 ms

1 ms

1 ms

1 ms

system overhead

4 ms

4 ms

4 ms

4 ms

4 ms

continuous task

5

10

15

20

25

elapsed time (ms)

1 ms

system overhead

1 ms

continuous task

5

10

15

20

25

elapsed time (ms)

periodic task

system overhead

5

10

15

20

25

continuous task

elapsed time (ms)