Place local i/o modules, Selecting a power supply – Rockwell Automation 1794-L34 FlexLogix Controller System User Manual User Manual

Page 54

Advertising
background image

Publication 1794-UM001G-EN-P - January 2007

54 Place, Configure, and Monitor I/O

Place Local I/O Modules

The FlexLogix controller supports a local DIN rail of as many as 8 I/O
modules and an extended-local DIN rail of as many as 8 I/O modules.
The second DIN rail is optional.

Selecting a Power Supply

In a FlexLogix system, select an Allen-Bradley power supply. In
applications that must be compliant with CSA requirements, use a
Separated Extra-Low Voltage (SELV) power supply that is compliant
with IEC 61010.1, Annex H.

When selecting power supplies:

• Provide power for the controller separately from the power for

the FLEX I/O modules. To provide power for FLEX I/O modules,
follow the guidelines in the documentation for those modules.

• When providing power for the 1794-FLA extended-local I/O

adapter, treat the adapter as a communication adapter, not as an
I/O module.

1794 FLEX power supplies

The following power supplies available for use with the FlexLogix
system.

See:

FLEX I/O Analog Modules User

Manual, 1794-6.5.2

FLEX I/O Digital Modules User

local DIN rail

extended-local DIN rail

Catalog number Nominal

input
voltage

Input
voltage
range

Maximum
real input
power

Maximum
apparent input
power

Maximum
transformer
load

Output current

1794-PS3

120/230V ac 85-265V ac

86W

205VA

250VA

3.0A @ 24V dc (horizontal
mount)

2.8A @ 24Vdc (non-horizontal
mount)

1794-PS13

36W

53VA

90VA

1.3A @ 24V dc

Advertising