Publication 1794-UM001G-EN-P - January 2007

FlexLogix Back-Up on DeviceNet 113

Table describes the possible values this message may return when
reading the back-up state of the DeviceNet scanner.

If the message reads
this value:

the back-up state of the DeviceNet scanner is:

0

Disabled

1

Primary scanner

2

Back-up scanner

3

Invalid primary node address (e.g. the node address cannot
be 62 or 63)

4

Faulted back-up scanner - CRC failure (e.g. the scanlists in
the scanners do not match)

5

Faulted back-up scanner - back-up node number failure (e.g.
the back-up scanner is not using a node number = the
primary node number + 1)

6

Back-up scanner pending primary detection

254

Attempting primary access

255

Attempting back-up access