Publication 1794-UM001G-EN-P - January 2007

Manage Controller Communications 49

Connection Overview

A Logix5000 system uses a connection to establish a communication
link between two devices. Connections can be:

• controller to local I/O modules or local communication modules
• controller to remote I/O or remote communication modules
• controller to remote I/O (rack-optimized) modules
• produced and consumed tags
• messages
• controller access by RSLogix 5000 programming software
• controller access by RSLinx software for HMI or other

applications

The limit of connections may ultimately reside in the communication
module you use for the connection. If a message path routes through
a communication module, the connection related to the message also
counts towards the connection limit of that communication module.

Other controllers and communication modules support different
maximum numbers of connections.

For more information...

The Logix5000 Controllers Design Considerations Reference Manual,
1756-RM094 describes how to optimize connection use.

See:

Logix5000 Controllers Design

Considerations Reference Manual,
1756-RM094

This device

Supports this many connections

FlexLogix controller

100

1788-CNx communication card

32

1788-DNBO communication card

2

1788-ENBT communication card

32