Chapter

2

Installing the 1756-HYD02 Module

What This Chapter Contains

This chapter describes how to install the 1756-HYD02 module.

The 1756-HYD02 module mounts in a ControlLogix chassis and uses a
removable terminal block (RTB) to connect all field-side wiring.

Before you install your module, make sure you:

• install and ground a ControlLogix chassis and power supply.
• order and receive an RTB, and its components, for your application.

For more information on all the ControlLogix chassis and power supplies, see
the ControlLogix Selection Guide, publication

1756-SG001

.

Note the Power
Requirements

This module receives power from the 1756 chassis power supply and requires
two sources of power from the backplane:

• 700mA at 5.1V
• 2.5 mA at 24V

Add this current to the requirements of all other modules in this chassis to
prevent overloading the backplane power supply.

For information about:

See page:

Installing the Module

14

Keying the Removable Terminal Block

15

Connecting Wiring

16

Assembling The Removable Terminal Block and
the Housing

23

Installing the Removable Terminal Block

26

Removing the Removable Terminal Block

28

Removing the Module from the Chassis

29