Rockwell Automation 1756-HYD02 ControlLogix Hydraulic Servo Module User Manual

Page 49

Advertising
background image

Publication 1756-UM525A-EN-P - June 2003

49

Using the 1756-HYD02 Module Features Chapter 4

EXAMPLE

In the following scenario, Compatible Keying allows I/O
communication
:

The module configuration is for a 1756-IB16D module with module

revision 2.1. The physical module is a 1756-IB16D module with
module revision 3.2. In this case, communication is allowed
because the major revision of the physical module is higher than
expected and the module determines that it is compatible with the
prior major revision.

IMPORTANT

Changing electronic keying selections online may cause the I/O
communication connection to the module to be disrupted and may
result in a loss of data.

Module Configuration

Vendor = Allen-Bradley
Product Type = Digital Input
Module
Catalog Number = 1756-IB16D
Major Revision = 2
Minor Revision = 1

Physical Module

Vendor = Allen-Bradley
Product Type = Digital Input
Module
Catalog Number = 1756-IB16D
Major Revision = 3
Minor Revision = 2

Communication is allowed

Advertising