Connecting ldts to your hydraulic module – Rockwell Automation 1756-HYD02 ControlLogix Hydraulic Servo Module User Manual

Page 21

Advertising
background image

Publication 1756-UM525A-EN-P - June 2003

21

Installing the 1756-HYD02 Module Chapter 2

Connecting LDTs to Your Hydraulic Module

Because the number of LDTs that you can connect to your 1756-HYD02
module is continually changing, we cannot list all the available LDTs here.
Figure shows the connections for two example LDT types–Temposonic and
Balluff–that were available for connection to the 1756-HYD02 module at the
time of this printing.

Table lists the LDT connections.

IMPORTANT

Remember, there are other suppliers with compatible LDTs.
Before connecting an LDT to your module, we recommend you
make sure it is the best available LDT for your application.

Also, when wiring an LDT to your module, always follow the
LDT manufacturer’s instructions on making connections.

Temposonics II,

RPM or DPM

Balluff BTL type

43473

Interrogate

+/-12V dc

Output Pulse

Ground

Interrogate (+)

+24V

Pulse (+)
Output

Interrogate (-)

Pulse (-)
Output

Ground

Interrogate (+)

+15V

Pulse (+)
Output

Interrogate (-)

Pulse (-)
Output

Ground

-15V

24V Connections

+/- 15V Connections

No shield connections on these examples

LDT Connections for Fabricating Your Own LDT Cable

Function

(1)

1756-HYD02 RTB Wiring (Numbers below

represent terminal numbers)

Temposonics II

(2)

RPM or DPM

Balluff

BTL type

Channel 0

Channel 1

24V dc

+/- 15V dc

(+) Interrogate

26

25

9 - Yellow

1 - Yellow

1 - Yellow

(-) Interrogate

28

27

10 - Green

3 - Pink

3 - Pink

Power Supply

N/A

5 - Red (+/-12V)

7 - Brown (+24V)

7 - Brown (+15V)
8 - White (-15V)

Ground

34

33

1 - White

6 - Blue
8 - White

6 - Blue

Output Pulse

30 (+)
32 (-)

29 (+)
31 (-)

8 - Purple

2 - Gray (+)
5 - Green (-)

2 - Gray (+)
5 - Green (-)

(1)

(+) and (-) wires of the same function should be a twisted pair within the cable.

(2)

Do not connect to pins 2, 3, 4, 6 or 7