Choosing the
Extended-Depth Housing
There are two housing options you must consider when wiring your
ControlLogix Hydraulic Servo module. When you order an RTB for your I/O
module, you receive a standard-depth housing with the RTB. If your
application uses heavy gauge wiring, you can order an extended-depth housing.
This housing does not come with an RTB.
You can use one of the housings listed below:
The figure below shows the difference, in terms of capacity, between the
housing options.
This housing:
should be used with this RTB:
and allows up to this
capacity of wires:
1756-TBCH
Cage clamp
336 sq. mm
1756-TBS6H
Spring clamp
1756-TBE
Any RTB using heavy gauge wiring
628 sq. mm
IMPORTANT
The housings shown are used with a spring clamp RTB, but the
capacity for each remains the same regardless of RTB type.
Standard-Depth Housing
Extended-Depth Housing
30484-M
Maximum Area = 336 sq. mm
36 - 18AWG wires
23 - 14AWG wires
Maximum Area = 628 sq. mm
40 - 14AWG wires
IMPORTANT
The housings use the following maximum areas:
• standard-depth housing maximum area = 336 sq. mm
• extended-depth housing maximum area = 628 sq. mm