24

Publication 1756-UM525A-EN-P - June 2003

Chapter 2 Installing the 1756-HYD02 Module

Choosing the
Extended-Depth Housing

There are two housing options you must consider when wiring your
ControlLogix Hydraulic Servo module. When you order an RTB for your I/O
module, you receive a standard-depth housing with the RTB. If your
application uses heavy gauge wiring, you can order an extended-depth housing.
This housing does not come with an RTB.

You can use one of the housings listed below:

The figure below shows the difference, in terms of capacity, between the
housing options.

This housing:

should be used with this RTB:

and allows up to this
capacity of wires:

1756-TBCH

Cage clamp

336 sq. mm

1756-TBS6H

Spring clamp

1756-TBE

Any RTB using heavy gauge wiring

628 sq. mm

IMPORTANT

The housings shown are used with a spring clamp RTB, but the
capacity for each remains the same regardless of RTB type.

Standard-Depth Housing

Extended-Depth Housing

30484-M

Maximum Area = 336 sq. mm

36 - 18AWG wires

23 - 14AWG wires

Maximum Area = 628 sq. mm

40 - 14AWG wires

IMPORTANT

The housings use the following maximum areas:

• standard-depth housing maximum area = 336 sq. mm

• extended-depth housing maximum area = 628 sq. mm