EXAMPLE

In the following scenario, Disable Keying allows I/O
communication
:

The module configuration is for a 1756-IA16 digital input module.

The physical module is a 1756-IB16 digital input module. In this
case, communication is allowed because the two digital modules
share common data formats.

IMPORTANT

Changing electronic keying selections online may cause the I/O
communication connection to the module to be disrupted and may
result in a loss of data.

Module Configuration

Vendor = Allen-Bradley
Product Type = Digital Input
Module
Catalog Number = 1756-IA16
Major Revision = 2
Minor Revision = 1

Physical Module

Vendor = Allen-Bradley
Product Type = Digital Input
Module
Catalog Number = 1756-IB16
Major Revision = 3
Minor Revision = 2

Communication is allowed